ACSS/TW Aluminum Conductor Steel Supported Trapezoidal Wire

Home > Products > Bare Conductor > ACSS/TW Aluminum Conductor Steel Supported Trapezoidal Wire

ACSS/TW Aluminum Conductor Steel Supported Trapezoidal Wire

ACSS/TW – more conductivity, less sag.

Compact design, high-temp performance.

Upgrade lines with ACSS/TW efficiency.

Trapezoidal wire for tighter packing & higher ampacity.

Get ACSS/TW direct from factory – ASTM certified.

Application

ACSS/TW (Aluminium Conductor Steel Supported / Trapezoidal Wire) is a high-temperature, low-loss overhead transmission conductor consisting of annealed aluminum trapezoidal wires stranded on a steel core. Its unique trapezoidal conductor structure (TW) can accommodate more aluminum at the same outer diameter, increase current carrying capacity and reduce corona and resistance losses.

Compared with traditional ACSR, ACSS/TW can operate for a long time in an environment up to 250°C without losing mechanical properties, and is suitable for line capacity expansion or new high-load lines. Its aluminum wire is fully annealed, soft and does not creep, and the steel core bears all the tension, ensuring that the line remains stable at high temperatures.

The trapezoidal wire design increases the aluminum cross-sectional area while maintaining the same outer diameter, making it convenient to upgrade old lines without changing towers. Compared with ACSS, ACSS/TW further optimizes the conductor structure, improves transmission efficiency and reduces energy consumption.

ACSS/TW conductors are widely used in high-voltage and ultra-high-voltage transmission lines and line projects under complex environmental conditions. They comply with international standards such as ASTM B857 and B856 and are an ideal choice for high-temperature capacity expansion and energy-saving transformation of modern power grids.

Specifications

FeatureACSS/AW (B 857)ACSS (galv. steel)ACSROuter LayersCore (Support)
Temp. ratingUp to 250°CUp to 250°C~90°CFully annealed aluminum (1350-O or 1350-H0)Aluminum-Clad Steel (ACS), with metallurgically bonded aluminum layer
Core typeAluminum-clad steelGalvanized steelGalvanized steel  
Sag under loadVery lowLowHigh  
Corrosion resistance✅ Very highModerateModerate  
Creep resistanceExcellentExcellentModerate  

 

Parameter

CodeConductor SizeAluminumSteel Core StrandingNominal MassRated StrengthNominal Outside Diameter,Nominal DC Resistance at 20℃
WordStranding
 No. of Aluminum WiresNo. ofNo. ofIndividual Strand Wire DiameterGA2/ MA2GA3/ MA3AW2
 LayersWires
 MCM   mmkg/km kN kN kN mmΩ/km
Partridge266.818272.00251939.5943.1537.3614.730.206
Oriole336.417272.6978365.8372.563.1617.530.1625
Flicker47718272.38891157.8263.1655.619.810.116
Hawk47718272.67597569.3976.0666.2820.070.1153
Hen47717273.203111093.41100.9789.421.080.1146
Parakeet556.518272.578106267.6173.8464.9421.340.099
Dove556.520272.891113780.9588.5277.8421.590.0987
Rook63618272.756121776.9584.5174.2822.610.0867
Grosbeak63620273.089129992.0799.6488.5223.110.0863
Tern79517272.25132663.1667.6160.0524.380.0697
Puffin79518272.814144984.0791.6381.424.890.0697
Condor79520273.081151896.52103.6492.9625.150.0693
Drake79520273.4541623115.2124.54108.5325.650.069
Mallard795222192.4821836152.57168.58146.3426.670.0688
Phoenix95430372.126153063.1667.6160.4926.670.0587
Rail95432372.466159874.2880.0672.0626.920.0583
Cardinal95420273.3761826115.65124.54109.4227.430.0577
Snowbird1033.530372.212165868.572.9565.8327.690.054
Ortolan1033.532372.565173180.5186.7478.2827.940.054
Curlew1033.521273.5131973125.43134.77116.0928.70.0533
Avocet111330372.296178472.577.8470.7228.70.05
Bluejay111333372.664186486.7493.4184.0728.960.05
Finch1113383192.1892123135.22147.67128.130.230.0497
Oxbird1192.530372.377191277.8483.1875.6229.720.0467
Bunting1192.533372.756199792.96100.0890.2929.970.0467
Grackle1192.5383192.2662275145157.913730.990.0467
Scissortail127230372.456204083.1888.9680.9530.480.044
Bittern127235372.847213199.19106.7596.0830.990.0437
Pheasant1272393192.3392425151.68165.91145.89320.0437
Dipper1351.535372.9342263105.42113.42102.3320.0413
Martin1351.5393192.412577161.02176.14155.2433.020.041
Bobolink143136373.022397111.64120.1108.0932.770.039
CodeConductor SizeAluminumSteel Core StrandingNominal MassRated StrengthNominal Outside Diameter,Nominal DC Resistance at 20℃
WordStranding
 No. of Aluminum WiresNo. ofNo. ofIndividual Strand Wire DiameterGA2/ MA2GA3/ MA3AW2
 LayersWires
 MCM   mmkg/kmkNkNkNmmΩ/km
Plover1431393192.4822729170.8186.37164.1334.040.0387
Lapwing159036373.1832664124.1131.66120.134.540.035
Falcon1590423192.6163033189.48207.28182.8135.810.035
Chukar1780373192.223067157.01169.91149.4536.830.0313
Bluebird2156644192.4413738187.26202.38181.0340.890.026
CodeConductor SizeAluminumSteel Core StrandingNominal MassRated StrengthNominal Outside Diameter,Nominal DC Resistance at 20℃
WordStranding
 No. of Aluminum WiresNo. ofNo. ofIndividual Strand Wire DiameterGA2/ MA2GA3/ MA3AW2
 LayersWires
 MCM   mmkg/kmkNkNkNmmΩ/km
Mohawk571.718272.616109269.3976.0666.7221.590.0963
Calumet565.320272.911115581.8489.8578.7321.840.0973
Mystic666.620272.822127480.9588.5277.8423.110.0827
Oswego664.820273.16135996.52104.0892.9623.620.0827
Maumee768.220273.035146993.41102.389.8524.890.0717
Wabash762.820273.3811558110.76119.21104.0825.150.072
Kettle957.232372.471160474.7380.5172.526.920.0583
Fraser946.735372.931169693.85101.8690.2927.430.0587
Columbia966.221273.3991845117.43125.88110.7627.690.0573
Suwannee959.622273.7921960136.55147.23125.4328.190.0573
108020272.624180284.0790.7481.8428.70.0517
Cheyenne1168.130372.352187376.5181.474.2829.460.0477
Genesee115833372.738194591.1898.388.5229.720.048
Hudson1158.425273.7262214138.33149.01127.6630.480.0477
Catawba127230372.456204083.1888.9680.9530.480.044
Nelson1257.135372.832210798.3105.8695.1930.730.0443
Yukon1233.6383192.3112357147.67161.46142.3431.750.045
Truckee1372.530372.55220189.8595.6387.1831.750.0407
CodeConductor SizeAluminumSteel Core StrandingNominal MassRated StrengthNominal Outside Diameter,Nominal DC Resistance at 20℃
WordStranding
 No. of Aluminum WiresNo. ofNo. ofIndividual Strand Wire DiameterGA2/ MA2GA3/ MA3AW2
 LayersWires
 MCM   mmkg/kmkNkNkNmmΩ/km
Mackenzie1359.736372.9442278106.31114.31102.75320.041
Thames1334.6393192.3982546159.24173.92153.4632.770.0417
St.Croix1467.833372.644235696.08102.7593.4132.770.038
Miramichi1455.336373.0482439113.87120.54110.3133.020.0383
Merrimack1433.6393192.4842735170.8186.82164.5834.040.0387
Platte156933372.7282516102.75109.4299.6433.780.0357
Potomac1557.436373.1522610121.43128.99117.8734.290.0357
Rio Grande1533.3393192.572925183.26200.16176.1435.050.0363
Schuylkil1657.436373.2512777129.44137.44125.4335.310.0337
Pecos1622393192.7033132200.16219.29192.636.070.034
Pee Dee1758.637373.352946137.44145.89130.7736.320.0317
James1730.6393192.7313302206.39225.96198.8337.340.032
Athabaska1949.642373.5363269152.57162.3514138.10.0287
Cumberland1926.9423192.8783674229.52250.87221.0739.370.0287
Powder2153.8644192.4413735187.26202.38181.0340.640.026
Santee2627.3644192.6974558228.18247.31221.0744.70.0213

 

PDF Download