Aerial Bundled Cable (Complying with IEC / BS / AS/NZS / NFC / HD Standards)
Home > Products > Aerial Bunch Cable > Aerial Bundled Cable (Complying with IEC / BS / AS/NZS / NFC / HD Standards)
Aerial Bundled Cable (Complying with IEC / BS / AS/NZS / NFC / HD Standards)
ABC cable designed for safe overhead power distribution.
Standards-compliant bundled cable for urban and rural networks.
UV-resistant and insulated conductors for aerial installations.
Low-maintenance ABC cable ideal for harsh outdoor conditions.
Reliable and space-saving solution for overhead LV systems.
Application
Aerial Bundled Cable (ABC) is a compact, insulated overhead power cable system designed for low and medium voltage distribution in urban, rural, and remote areas. Unlike bare conductor systems, ABC cables feature tightly bundled insulated conductors, significantly reducing the risk of short circuits, electrocution, and line faults due to tree contact or harsh weather.
Constructed with aluminum or aluminum alloy conductors, and insulated with XLPE, HDPE, or PE, ABC cables are lightweight, corrosion-resistant, and easy to install on poles without requiring heavy infrastructure. Some designs include a messenger wire or neutral conductor for added mechanical support.
These cables are widely used for overhead service lines, temporary connections, and grid extensions in challenging terrains. Their insulated design enables closer installation clearances, improves public safety, and reduces power outages due to external interference.
ABC systems are manufactured in accordance with multiple global standards including IEC 60228, BS 7870, AS/NZS 3560.1, NFC 33-209, and HD 626, ensuring adaptability across international markets.
Aerial Bundled Cables offer a cost-effective, reliable, and safer alternative to traditional bare overhead lines, particularly in densely populated or forested environments.
Specifications
| Standard | Conductor & Insulation Material | Typical Voltage & Applications |
|---|---|---|
| IEC 60502-1 / IEC 60228 | – Phase: Stranded Aluminum 1350– Messenger: Bare Aluminum Alloy or Galvanized Steel– Insulation: XLPE | – 0.6/1 kV LV ABC for overhead power distribution in residential and urban areas |
| BS 7870-5 | – Conductors: Stranded Aluminum Class 2– Neutral: Steel core or Aluminum alloy– Insulation: XLPE / HDPE | – Low-voltage ABC in UK distribution networks- Designed for resistance to mechanical stress |
| AS/NZS 3560 | – Phase: 1350-H19 Aluminum– Messenger: Galvanized Steel Wire or Insulated Neutral– Insulation: UV-stabilized XLPE | – Used in Australia/NZ for 0.6/1 kV & 11 kV ABC– Ideal for bushfire-prone areas |
| NFC 33-209 (France) | – Conductors: Stranded Aluminum or Alloy– Messenger: Insulated Neutral (self-supporting)- Insulation: XLPE | – 0.6/1 kV LV ABC– Widely used in French-speaking regions for safer overhead wiring |
| HD 626 (EU) | – Phase: Aluminum Class 2– Messenger: Steel-reinforced Aluminum– Insulation: XLPE | – European standard for insulated overhead cables, both single and bundled conductors |
Parameter
AS/NZS 3560.1-Australian and New Zealand Standard: General Specification for ABC Cables (LV) 🇦🇺 Australia, 🇳🇿 New Zealand
| 0.6/1 KV ABC (Aerial Bundle) Cable- AS/NZS 3560.1 (AL/XLPE) | ||||
| Number of Cores x Nominal Cross Section | Overall Diameter | Weight | Minimum Breaking Load | Current Rating |
| No.mm^2 | mm | Kg/Km | KN | A |
| 2×16 RM | 15 | 140 | 4.4 | 78 |
| 2×25 RM | 17.6 | 210 | 7 | 105 |
| 2×35 RM | 19.6 | 270 | 9.8 | 125 |
| 2×50 RM | 22.8 | 370 | 11.4 | 150 |
| 2×95 RM | 30.6 | 680 | 15.3 | 230 |
| 3×25 RM | 19 | 310 | 8.8 | 97 |
| 3×35 RM | 21.1 | 410 | 9.8 | 120 |
| 3×50 RM | 24.6 | 550 | 11.4 | 140 |
| 4×16 RM | 18.1 | 290 | 8.8 | 74 |
| 4×25 RM | 21.2 | 410 | 14 | 97 |
| 4×35 RM | 23.7 | 550 | 19.6 | 120 |
| 4×50 RM | 27.5 | 740 | 28 | 140 |
| 4×70 RM | 31.9 | 1000 | 39.2 | 175 |
| 4×95 RM | 36.9 | 1370 | 53.2 | 215 |
| 4×120 RM | 40.6 | 1690 | 67.2 | 250 |
| 4×150 RM | 43.9 | 2020 | 84 | 280 |
AS/NZS 3599.1- Australian and New Zealand Standard: Medium Voltage ABC (MV, 6.35/11kV, etc.) 🇦🇺 Australia, 🇳🇿 New Zealand-AL/XLPE /HDPE Non-Screened Cables
| 6.35/11kV & 12.7/22kV Al/XlPE /HDPE Non-Screened Cables ABC Cable-AS/NZS 3599.1 Standard | ||||||||||
| number of cores x nominal cross section | Nominal conductor diameter | Nominal insulation thickness | Nominal insulation screen thickness | Nominal sheath thickness | AAAC/1120 support conductor size | Nominal overall diameter | Weight | Continuous current rating, A | ||
| Still air | 1m/s wind | 2m/s wind | ||||||||
| mm^2 | mm | mm | mm | mm | No/mm | mm | kg/km | A | A | A |
| 6.35/11kV | ||||||||||
| 3×35 | 6.9 | 3.4 | 0.8 | 1.2 | 7/4.75 | 52.4 | 1370 | 110 | 155 | 185 |
| 3×50 | 8.1 | 3.4 | 0.8 | 1.2 | 7/4.75 | 54.6 | 1530 | 130 | 185 | 225 |
| 3×70 | 9.7 | 3.4 | 0.8 | 1.2 | 7/4.75 | 57.8 | 1790 | 160 | 235 | 280 |
| 3×95 | 11.4 | 3.4 | 0.8 | 1.2 | 7/4.75 | 61.3 | 2100 | 195 | 285 | 345 |
| 3×120 | 12.8 | 3.4 | 0.8 | 1.2 | 19/3.50 | 67.3 | 2540 | 230 | 335 | 405 |
| 3×150 | 14.2 | 3.4 | 0.8 | 1.2 | 19/3.50 | 70.1 | 2840 | 255 | 380 | 460 |
| 3×185 | 15.7 | 3.4 | 0.8 | 1.2 | 19/3.50 | 73.1 | 3190 | 295 | 440 | 530 |
| 12.7/22kV | ||||||||||
| 3×35 | 6.9 | 5.5 | 0.8 | 1.2 | 7/4.75 | 61 | 1780 | 110 | 155 | 180 |
| 3×50 | 8.1 | 5.5 | 0.8 | 1.2 | 7/4.75 | 63.3 | 1970 | 130 | 185 | 220 |
| 3×70 | 9.7 | 5.5 | 0.8 | 1.2 | 7/4.75 | 66.5 | 2260 | 160 | 230 | 275 |
| 3×95 | 11.4 | 5.5 | 0.8 | 1.2 | 7/4.75 | 69.9 | 2600 | 195 | 285 | 335 |
| 3×120 | 12.8 | 5.5 | 0.8 | 1.2 | 19/3.50 | 75.9 | 3070 | 225 | 330 | 395 |
| 3×150 | 14.2 | 5.5 | 0.8 | 1.2 | 19/3.50 | 78.7 | 3390 | 255 | 375 | 450 |
| 3×185 | 15.7 | 5.5 | 0.8 | 1.2 | 19/3.50 | 81.7 | 3760 | 290 | 435 | 520 |
AS/NZS 3599.1 Australian and New Zealand Standard: Medium Voltage ABC (MV, 6.35/11kV, etc.) 🇦🇺 Australia, 🇳🇿 New Zealand-AL/XLPE /CWS/HDPE Screened Cables
| 6.35/11kV & 12.7/22kV Al/XlPE /HDPE Non-Screened Cables ABC Cable-AS/NZS 3599.1 Standard | ||||||||||
| number of cores x nominal cross section | Nominal conductor diameter | Nominal insulation thickness | Nominal insulation screen thickness | Nominal sheath thickness | AAAC/1120 support conductor size | Nominal overall diameter | Weight | Continuous current rating, A | ||
| Still air | 1m/s wind | 2m/s wind | ||||||||
| mm^2 | mm | mm | mm | mm | No/mm | mm | kg/km | A | A | A |
| 6.35/11kV | ||||||||||
| 3×35 | 6.9 | 3.4 | 0.8 | 1.2 | 7/4.75 | 52.4 | 1370 | 110 | 155 | 185 |
| 3×50 | 8.1 | 3.4 | 0.8 | 1.2 | 7/4.75 | 54.6 | 1530 | 130 | 185 | 225 |
| 3×70 | 9.7 | 3.4 | 0.8 | 1.2 | 7/4.75 | 57.8 | 1790 | 160 | 235 | 280 |
| 3×95 | 11.4 | 3.4 | 0.8 | 1.2 | 7/4.75 | 61.3 | 2100 | 195 | 285 | 345 |
| 3×120 | 12.8 | 3.4 | 0.8 | 1.2 | 19/3.50 | 67.3 | 2540 | 230 | 335 | 405 |
| 3×150 | 14.2 | 3.4 | 0.8 | 1.2 | 19/3.50 | 70.1 | 2840 | 255 | 380 | 460 |
| 3×185 | 15.7 | 3.4 | 0.8 | 1.2 | 19/3.50 | 73.1 | 3190 | 295 | 440 | 530 |
| 12.7/22kV | ||||||||||
| 3×35 | 6.9 | 5.5 | 0.8 | 1.2 | 7/4.75 | 61 | 1780 | 110 | 155 | 180 |
| 3×50 | 8.1 | 5.5 | 0.8 | 1.2 | 7/4.75 | 63.3 | 1970 | 130 | 185 | 220 |
| 3×70 | 9.7 | 5.5 | 0.8 | 1.2 | 7/4.75 | 66.5 | 2260 | 160 | 230 | 275 |
| 3×95 | 11.4 | 5.5 | 0.8 | 1.2 | 7/4.75 | 69.9 | 2600 | 195 | 285 | 335 |
| 3×120 | 12.8 | 5.5 | 0.8 | 1.2 | 19/3.50 | 75.9 | 3070 | 225 | 330 | 395 |
| 3×150 | 14.2 | 5.5 | 0.8 | 1.2 | 19/3.50 | 78.7 | 3390 | 255 | 375 | 450 |
| 3×185 | 15.7 | 5.5 | 0.8 | 1.2 | 19/3.50 | 81.7 | 3760 | 290 | 435 | 520 |
IEC 60502-ES/LVC(AL/XLPE) International Electrotechnical Commission Standard (0.6/1kV ~ 30kV) 🌍 Widely used internationally: Africa, Asia, Europe, Latin America, Middle East, CIS countries, etc.
| 0.6/1 KV ABC-Aerial Bundled Cable- ES/LVC- IEC 60502-(AL/XLPE) | ||||
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
| mm^2 | kN | A | mm | kg/km |
| 4×25 RM | 3.5 | 84 | 21.5 | 420 |
| 4×35 RM | 4.9 | 104 | 23.9 | 550 |
| 4×120+1×25 RM | 16.8 | 246 | 43.8 | 1800 |
| 4×185+1×25 RM | 25.9 | 332 | 50.7 | 2700 |
IEC 60502 & TNB-(AL/PE) International Electrotechnical Commission Standard (0.6/1kV ~ 30kV) 🌍 Widely used internationally: Africa, Asia, Europe, Latin America, Middle East, CIS countries, etc.
| 0.6/1 KV ABC-Aerial Bundle Cable- IEC 60502 & TNB-(AL/PE) | ||||
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
| mm^2 | kN | A | mm | kg/km |
| 1×16+1x 25 RM | 6.4 | 61 | 15.3 | 160 |
| 3×16+1x 25 RM | 6.4 | 61 | 19 | 290 |
| 3×25+1x 25 RM | 6.4 | 84 | 23.2 | 400 |
| 3×35+1x 25 RM | 6.4 | 104 | 25.6 | 500 |
| 3×50+1x 35 RM | 8.9 | 129 | 30 | 680 |
| 3×70+1x 50 RM | 12.1 | 167 | 34.9 | 920 |
| 3×95+1x 70 RM | 18 | 209 | 40.6 | 1270 |
| 3×120+1x 70 RM | 18 | 246 | 44.1 | 1510 |
| 3×150+1x 95 RM | 24.2 | 283 | 49.2 | 1870 |
| 3×185+1×120 RM | 30.8 | 332 | 54.9 | 2340 |
| 3×25+1×25+1×16 RM | 6.4 | 84 | 23.2 | 470 |
| 3×35+1×25+1×16 RM | 6.4 | 104 | 25.6 | 560 |
| 3×50+1×35+1×16 RM | 8.9 | 129 | 30 | 740 |
| 3×70+1×50+1×16 RM | 12.1 | 167 | 34.9 | 980 |
| 3×95+1×70+1×16 RM | 18 | 209 | 40.6 | 1330 |
| 3×120+1×70+1×16 RM | 18 | 246 | 44.1 | 1580 |
| 3×150+1×95+1×16 RM | 24.2 | 283 | 49.2 | 1940 |
| 3×185+1×120+1×16 RM | 30.8 | 332 | 54.9 | 2410 |
IEC 60502-1 6.35/11kV IEC medium voltage overhead insulated cable design voltage 🌍 Same as above Indicates that the medium voltage ABC conductor is suitable for 6.35/11kV (phase voltage/line voltage) system
| IEC 60502 6.35/11kV 19/33 kV ABC for Overhead Distribution Lines | |||||||
| IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines | |||||||
| Number of Cores x Nominal Cross Section | Phase Conductor | Messenger Suspension Unit | Continuous current rating at 300C ambient temp | ||||
| Stranding | Nominal Sectional Area | Maximum Conductor Resistance | Stranding | Nominal Sectional Area | Breaking Load | ||
| No.mm^2 | No.mm | mm^2 | Ω/Km | No.mm | mm^2 | KN | A |
| 3X50 + 1X25 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 116 |
| 3X70 + 1X50 | 19/.14 | 70 | 0.443 | 7/3.15 | 50 | 62 | 210 |
| 3X95+ 1X50 | 19/2.52 | 95 | 0.32 | 7/3.0 | 50 | 60 | 173 |
| 3X185+1X120 | 37/2.52 | 185 | 0.164 | 7/4.67 | 120 | 150 | 259 |
| 3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 365 |
| 3X240 +1X50 | 61/2.25 | 240 | 0.125 | 7/3.15 | 50 | 62 | 500 |
| IEC 60502 19/33 kV ABC for Overhead Distribution Lines | |||||||
| Number of Cores x Nominal Cross Section | Phase Conductor | Messenger Suspension Unit | Continuous current rating at 300C ambient temp | ||||
| Stranding | Nominal Sectional Area | Maximum Conductor Resistance | Stranding | Nominal Sectional Area | Breaking Load | ||
| No.mm^2 | No.mm | mm^2 | Ω/Km | No.mm | mm^2 | KN | A |
| 3X50 + 1X50 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 165 |
| 3X150+ 1X50 | 37/2.25 | 150 | 0.206 | 7/3.0 | 50 | 60 | 315 |
| 3X185+1X70 | 37/2.52 | 185 | 0.164 | 7/3.57 | 70 | 91 | 355 |
| 3X70 +1X50 | 19/2.14 | 7 | 0.443 | 7/3.15 | 50 | 62 | 250 |
| 3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 370 |
BS 7870-5(AL/XLPE) British Standard: ABC Cable Special Standard 🇬🇧 UK, 🇮🇳 India, 🇳🇬 Nigeria, 🇿🇦 South Africa, 🇵🇰, 🇧🇩, 🇰🇪 and other Commonwealth countries
| 0.6/1 KV ABC –Aerial Bundled Cables- BS 7870-5 (AL/XLPE) | |||||
| Number of Cores x Nominal Cross Section | Overall Diameter | Weight | Maximum Conductor Resistance | Minimum Breaking Load | Current Rating |
| No.mm^2 | mm | Kg/Km | Ω/Km | KN | A |
| 1×16 RM | 8 | 74 | 1.91 | 2.5 | 72 |
| 1×25 RM | 9 | 106 | 1.2 | 4 | 107 |
| 1×35 RM | 10.5 | 138 | 0.868 | 5.5 | 132 |
| 1×50 RM | 11.8 | 182 | 0.641 | 8 | 165 |
| 1×70 RM | 13 | 252 | 0.443 | 10.7 | 205 |
| 1×95 RM | 15.4 | 333 | 0.32 | 13.7 | 240 |
| 1×120 RM | 17 | 408 | 0.253 | 18.6 | 290 |
| 1×150 RM | 19 | 502 | 0.206 | 23.2 | 334 |
| 1×185 RM | 21 | 611 | 0.164 | 28.7 | 389 |
| 1×240 RM | 24 | 801 | 0.125 | 37.2 | 467 |
| 2×16 RM | 15.6 | 147 | 1.91 | 2.5 | 72 |
| 2×25 RM | 18 | 208 | 1.2 | 4 | 107 |
| 2×35 RM | 20 | 277 | 0.868 | 5.5 | 132 |
| 2×50 RM | 23.5 | 361 | 0.641 | 8 | 165 |
| 2×70 RM | 25.4 | 505 | 0.443 | 10.7 | 205 |
| 2×95 RM | 30.3 | 666 | 0.32 | 13.7 | 240 |
| 2×150 RM | 38 | 1004 | 0.206 | 23.2 | 334 |
| 4×16 RM | 18.8 | 286 | 1.91 | 2.5 | 72 |
| 4×25 RM | 21.2 | 430 | 1.2 | 4 | 107 |
| 4×35 RM | 24.1 | 553 | 0.868 | 5.5 | 132 |
| 4×50 RM | 27.8 | 746 | 0.641 | 8 | 165 |
| 4×70 RM | 31.8 | 1009 | 0.443 | 10.7 | 205 |
| 4×95 RM | 37.8 | 1332 | 0.32 | 13.7 | 240 |
| 4×120 RM | 54.4 | 1632 | 0.253 | 18.6 | 290 |
| 4×50 + 1×25 RM | 31.9 | 814 | 0.641/1.200 | 8.0/4.0 | 165/107 |
| 4×50 + 1×35 RM | 31.9 | 845 | 0.641/0.868 | 8.5/5.5 | 165/132 |
| 4×70 + 1×25 RM | 36 | 1105 | 0.443/1.200 | 10.7/4.0 | 205/107 |
| 4×70 + 2×25 RM | 40 | 1217 | 0.443/1.200 | 10.7/4.0 | 205/107 |
| 4×95 + 1×25 RM | 41.8 | 1438 | 0.320/1.200 | 13.7/4.0 | 240/107 |
| 4×95 + 2×25 RM | 42 | 1544 | 0.320/1.200 | 13.7/4.0 | 240/107 |
| 4×120 + 1×25 RM | 59 | 2050 | 0.253/1.200 | 18.6/4.0 | 290/107 |
NFC 33-209(AL/XLPE) French standard: ABC overhead cable specification 🇫🇷 France, 🇲🇦 Morocco, 🇩🇿 Algeria, 🇹🇳 Tunisia, French-speaking African countries
| 0.6/1 KV ABC –Aerial Bundled Cables – NFC 33-209 (AL/XLPE) | |||||
| Number of Cores x Nominal Cross Section | Overal Diameter | Weight | Maximum Conductor Resistance | Minimum Breaking Load | Current Rating |
| No.mm^2 | mm | Kg/Km | Ω/Km | KN | A |
| 2×10 RM | 12.8 | 93 | 3.08 | 1.5 | 38 |
| 4×10 RM | 15.4 | 183 | 3.08 | 1.5 | 38 |
| 2×16 RM | 14.8 | 129 | 1.91 | 2.3 | 72 |
| 2×16 RN + 2×1.5 RE | 14.8 | 176 | 1.910/12.100 | 2.3 | 72 |
| 4×16 RM | 17.8 | 257 | 1.91 | 2.3 | 72 |
| 4×16 RN + 2×1.5 RE | 17.8 | 304 | 1.910/12.100 | 2.3 | 72 |
| 2×25 RM | 18 | 202 | 1.2 | 3.8 | 107 |
| 2×25 RM + 2×1.5 RE | 18 | 249 | 1.200/12.100 | 3.8 | 107 |
| 4×25 RM | 21.7 | 404 | 1.2 | 3.8 | 107 |
| 4×25 RM + 2×1.5 RE | 21.7 | 451 | 1.200/12.100 | 3.8 | 107 |
| 2×35 RM | 20.8 | 269 | 0.868 | 5.2 | 132 |
| 2×35 RM + 2×1.5 RE | 20.8 | 316 | 0.868/12.100 | 5.2 | 132 |
| 4×35 RM | 25.1 | 539 | 0.868 | 5.2 | 132 |
| 4×35 RM + 2×1.5 RE | 25.1 | 586 | 0.868/12.100 | 5.2 | 132 |
| 2×50 RM | 23.4 | 352 | 0.641 | 7.6 | 165 |
| 2×50 RM + 2×1.5 RE | 23.4 | 399 | 0.641/12.100 | 7.6 | 165 |
| 1×54.6 RM + 3×25 RM | 21.7 | 507 | 0.630/1.200 | 3.8 | 107 |
| 1×54.6 RM + 3×25 RM + 1×16 RM | 24.3 | 573 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×25 RM + 2×16 RM | 29.7 | 639 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×25 RM + 3×16 RM | 31.1 | 705 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×35 RM | 25.1 | 615 | 0.630/0.868 | 5.2 | 132 |
| 1×54.6 RM + 3×35 RM + 1×16 RM | 28.1 | 680 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 2×16 RM | 34.3 | 748 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 3×16 RM | 35.9 | 814 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 1×25 RM | 28.1 | 714 | 0.630/0.868/1.200 | 5.2/3.8 | 132/107 |
| 1×54.6 RM + 3×50 RM | 28.2 | 741 | 0.630/0.641 | 7.6 | 165 |
| 1×54.6 RM + 3×50 RM + 1×16 RM | 31.6 | 806 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 2×16 RM | 38.6 | 875 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 3×16 RM | 40.4 | 940 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 1×25 RM | 31.6 | 841 | 0.630/0.641/1.200 | 7.6/3.8 | 165/107 |
| 1×54.6 RM + 3×70 RM | 33 | 950 | 0.630/0.443 | 10.2 | 205 |
| 1×54.6 RM + 3×70 RM + 1×16 RM | 37 | 1014 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 2×16 RM | 45.2 | 1083 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 3×16 RM | 47.3 | 1148 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 1×25 RM | 37 | 1048 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×70 RM + 2×25 RM | 45.2 | 1150 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×70 RM + 3×25 RM | 47.3 | 1250 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×95 RM | 37.4 | 1176 | 0.630/0.320 | 13.5 | 240 |
| 1×54.6 RM + 3×95 RM + 1×16 RM | 41.9 | 1243 | 0.630/0.320/1.910 | 13.5/2.3 | 240/72 |
HD 626 S1(AL/XLPE) European harmonized standard: ABC cable (cable system standard) 🇩🇪 🇫🇷 🇮🇹 🇪🇸 🇳🇱 🇧🇪 🇸🇪 etc. EU countries (EU/EFTA)
| 0.6/1 KV-ABC -Aerial Bundle Cable- HD 626 S1 (AL/XLPE) | ||||
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
| mm^2 | kN | A | mm | kg/km |
| 2x 16 RM | 1910 | 2,5 | 72 | 147 |
| 2x 25 RM | 1200 | 4,0 | 107 | 208 |
| 2x 35 RM | 0,868 | 5,5 | 132 | 277 |
| 2x 50 RM | 0,641 | 8,0 | 165 | 361 |
| 4x 16 RM | 1910 | 2,5 | 72 | 286 |
| 4x 25 RM | 1200 | 4,0 | 107 | 430 |
| 4x 35 RM | 0,868 | 5,5 | 132 | 553 |
| 4x 50 RM | 0,641 | 8,0 | 165 | 746 |
| 4x 70 RM | 0,443 | 10,7 | 205 | 1009 |
| 4x 95 RM | 0,320 | 13,7 | 240 | 1332 |
| 4x 120 RM | 0,253 | 18,6 | 290 | 1632 |
| 4x 35 + 1x 35 RM | 0,868 / 0,868 | 5,5 / 5,5 | 132 / 132 | 694 |
| 4x 50 + 1x 25 RM | 0,641 / 1,200 | 8,0 / 4,0 | 165 / 107 | 814 |
| 4x 50 + 1x 35 RM | 0,641 / 0,868 | 8,5 / 5,5 | 165 / 132 | 845 |
| 4x 70 + 1x 25 RM | 0,443 / 1,200 | 10,7 / 4,0 | 205 / 107 | 1105 |
| 4x 70 + 2x 25 RM | 0,443 / 1,200 | 10,7 / 4,0 | 205 / 107 | 1217 |
| 4x 70 + 1x 35 RM | 0,443 / 0,868 | 10,7 / 5,5 | 205 / 132 | 1150 |
| 4x 70 + 2x 35 RM | 0,443 / 0,868 | 10,7 / 5,5 | 205 / 132 | 1289 |
| 4x 95 + 1x 25 RM | 0,320 / 1,200 | 13,7 / 4,0 | 240 / 107 | 1438 |
| 4x 95 + 1x 35 RM | 0,320 / 0,868 | 13,7 / 5,5 | 240 / 132 | 1467 |
| 4x 95 + 2x 25 RM | 0,320 / 1,200 | 13,7 / 4,0 | 240 / 107 | 1544 |