Medium Voltage Cable Insulation Class 100% 133% ICEA S-94-649
Built for performance – 100% & 133% MV insulation grade.
Reliable medium voltage cables for critical power systems.
High dielectric strength, long-lasting protection.
MV cables with 100% & 133% insulation – safety guaranteed.
Certified medium voltage cables for underground & industrial use.
Application
100% and 133% insulation grade medium voltage (MV) power cables are designed for reliable power transmission in utility, industrial, and commercial distribution systems. They feature copper or aluminum conductors insulated with cross-linked polyethylene (XLPE), offering excellent dielectric strength, thermal stability, and long-term performance.
The 100% insulation grade is intended for grounded systems, where the cable operates with minimal overvoltage risk. The 133% grade is used in ungrounded or resistance-grounded systems, offering enhanced insulation thickness to withstand higher electrical stress and improve system reliability under fault conditions.
These cables support continuous operation at 90°C, with short-circuit temperature ratings up to 250°C, and are resistant to moisture, chemicals, and UV exposure. Optional shielding (e.g., copper tape, concentric wires) and PVC or PE outer sheaths provide additional protection and EMI reduction.
Specifications
| Aspect | Details & Applications |
| Conductor Material | Annealed copper or aluminum, solid or stranded, per IEC 60228 / ASTM B8 |
| Insulation Material | XLPE (Cross-linked Polyethylene) or EPR (Ethylene Propylene Rubber) – for high dielectric strength and thermal stability |
| Insulation Grade | 100% level: For systems with effectively grounded neutral133% level: For systems with ungrounded or intermittently grounded neutral |
| Voltage Range | Typically from 5 kV to 35 kV |
| Cable Type | Unarmoured or armoured, with metallic shield (copper tape or wire) |
| Sheath Material | PVC or LSZH (Low Smoke Zero Halogen) – protects against UV, chemicals, and mechanical damage |
| Standards | ICEA S-93-639 (NEMA WC74), ICEA S-97-682, IEEE 383, IEC 60502-2, AEIC CS8 |
| Electrical Properties | High dielectric strength, low partial discharge, stable under long-term loading |
| Temperature Rating | 90°C continuous operation; up to 250°C in short circuit (5 sec) |
| Shielding | Metallic shield ensures proper fault current path and controls electric field |
| Typical Applications | – Power distribution in utilities, industrial zones, substations- Installed in duct banks, conduits, direct buried or trays |
| Selection Tip | Use 100% insulation for grounded systems (more economical)Use 133% insulation where fault clearance may be delayed |
Parameter
15 kV Power Cable CU(AL)/XLPE/CWS/PVC Full Neutral
| 15 kV Power Cable CU(AL)/XLPE/CWS/PVC Full Neutral | ||||||||||||
| Conductor | Full Neutral | 100% Insulation Level | 133% Insulation Level | |||||||||
| Size | Area | Nominal Diameter | No. of wires | Size | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| AWG/kcmil | mm² | mm | AWG | mm | mm | mm | kg/km | mm | mm | mm | kg/km | |
| Copper Conductor | ||||||||||||
| 2 | 33.6 | 6.81 | 16 | 14 | 4.45 | 2.03 | 27.6 | 1143 | 5.59 | 2.03 | 30.1 | 1248 |
| 1 | 42.4 | 7.59 | 13 | 12 | 4.45 | 2.03 | 29.2 | 1345 | 5.59 | 2.03 | 31.8 | 1453 |
| 1/0 | 53.5 | 8.53 | 16 | 12 | 4.45 | 2.03 | 30.2 | 1567 | 5.59 | 2.03 | 32.7 | 1679 |
| 2/0 | 67.4 | 9.55 | 13 | 10 | 4.45 | 2.03 | 32.3 | 1883 | 5.59 | 2.03 | 34.8 | 1998 |
| 3/0 | 85 | 10.7 | 16 | 10 | 4.45 | 2.03 | 33.5 | 2229 | 5.59 | 2.03 | 36 | 2349 |
| 4/0 | 107 | 12.1 | 20 | 10 | 4.45 | 2.03 | 34.8 | 2668 | 5.59 | 2.03 | 37.3 | 2793 |
| 250 | 127 | 13.2 | 25 | 10 | 4.45 | 2.03 | 35.9 | 3128 | 5.59 | 2.03 | 38.4 | 3256 |
| Aluminum Conductor | ||||||||||||
| 2 | 33.6 | 6.81 | 10 | 14 | 4.45 | 2.03 | 27.6 | 812 | 5.59 | 2.03 | 30.1 | 917 |
| 1 | 42.4 | 7.59 | 13 | 14 | 4.45 | 2.03 | 28.4 | 919 | 5.59 | 2.03 | 30.9 | 1027 |
| 1/0 | 53.5 | 8.53 | 16 | 14 | 4.45 | 2.03 | 29.3 | 1036 | 5.59 | 2.03 | 31.8 | 1148 |
| 2/0 | 67.4 | 9.55 | 13 | 12 | 4.45 | 2.03 | 31.2 | 1204 | 5.59 | 2.03 | 33.7 | 1319 |
| 3/0 | 85 | 10.7 | 16 | 12 | 4.45 | 2.03 | 32.3 | 1380 | 5.59 | 2.03 | 34.9 | 1500 |
| 4/0 | 107 | 12.1 | 13 | 10 | 4.45 | 2.03 | 34.8 | 1642 | 5.59 | 2.03 | 37.3 | 1767 |
| 250 | 127 | 13.2 | 16 | 10 | 4.45 | 2.03 | 35.9 | 1877 | 5.59 | 2.03 | 38.4 | 2006 |
| 350 | 177 | 15.6 | 16 | 9 | 4.45 | 2.03 | 39 | 2304 | 5.59 | 2.03 | 42.1 | 2482 |
25 kV Power Cable CU(AL)/XLPE/CWS/PVC Full Neutral
| 25 kV Power Cable CU(AL)/XLPE/CWS/PVC Full Neutral | ||||||||||||
| Conductor | Full Neutral | 100% Insulation Level | 133% Insulation Level | |||||||||
| Size | Area | Nominal Diameter | No. of wires | Size | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| AWG/kcmil | mm² | mm | AWG | mm | mm | mm | kg/km | mm | mm | mm | kg/km | |
| Copper Conductor | ||||||||||||
| 1 | 42.4 | 7.59 | 13 | 12 | 6.6 | 2.03 | 33.7 | 1544 | – | – | – | – |
| 1/0 | 53.5 | 8.53 | 16 | 12 | 6.6 | 2.03 | 34.7 | 1772 | 8.13 | 2.03 | 38.3 | 1958 |
| 2/0 | 67.4 | 9.55 | 13 | 10 | 6.6 | 2.03 | 36.8 | 2094 | 8.13 | 2.03 | 41 | 2325 |
| 3/0 | 85 | 10.7 | 16 | 10 | 6.6 | 2.03 | 38 | 2449 | 8.13 | 2.03 | 42.2 | 2687 |
| 4/0 | 107 | 12.1 | 20 | 10 | 6.6 | 2.03 | 39.3 | 2897 | 8.13 | 2.03 | 43.5 | 3144 |
| 250 | 127 | 13.2 | 25 | 10 | 6.6 | 2.03 | 41 | 3403 | 8.13 | 2.03 | 44.6 | 3617 |
| Aluminum Conductor | ||||||||||||
| 1 | 42.4 | 7.59 | 13 | 14 | 6.6 | 2.03 | 32.9 | 1117 | ||||
| 1/0 | 53.5 | 8.53 | 16 | 14 | 6.6 | 2.03 | 33.8 | 1241 | 8.13 | 2.03 | 37.4 | 1427 |
| 2/0 | 67.4 | 9.55 | 13 | 12 | 6.6 | 2.03 | 35.7 | 1416 | 8.13 | 2.03 | 39.9 | 1646 |
| 3/0 | 85 | 10.7 | 16 | 12 | 6.6 | 2.03 | 36.8 | 1599 | 8.13 | 2.03 | 41 | 1837 |
| 4/0 | 107 | 12.1 | 13 | 10 | 6.6 | 2.03 | 39.3 | 1870 | 8.13 | 2.03 | 43.5 | 2117 |
| 250 | 127 | 13.2 | 16 | 10 | 6.6 | 2.03 | 41 | 2152 | 8.13 | 2.03 | 44.6 | 2366 |
| 350 | 177 | 15.6 | 16 | 9 | 6.6 | 2.03 | 44 | 2598 | 8.13 | 2.79 | 49.4 | 3020 |
35 kV Power Cable CU(AL)/XLPE/CWS/PVC Full Neutral
| 35 kV Power Cable CU(AL)/XLPE/CWS/PVC Full Neutral | ||||||||||||
| Conductor | Full Neutral | 100% Insulation Level | 133% Insulation Level | |||||||||
| Size | Area | Nominal Diameter | No. of wires | Size | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| AWG/kcmil | mm² | mm | AWG | mm | mm | mm | kg/km | mm | mm | mm | kg/km | |
| Copper Conductor | ||||||||||||
| 1/0 | 53.5 | 8.53 | 16 | 12 | 8.76 | 2.03 | 40.3 | 2075 | 10.67 | 2.03 | 43.8 | 2286 |
| 2/0 | 67.4 | 9.55 | 13 | 10 | 8.76 | 2.03 | 42.4 | 2405 | 10.67 | 2.03 | 45.9 | 2623 |
| 3/0 | 85 | 10.7 | 16 | 10 | 8.76 | 2.03 | 43.6 | 2770 | 10.67 | 2.79 | 48.9 | 3187 |
| 4/0 | 107 | 12.1 | 20 | 10 | 8.76 | 2.03 | 44.9 | 3229 | 10.67 | 2.79 | 50.2 | 3658 |
| 250 | 127 | 13.2 | 25 | 10 | 8.76 | 2.03 | 46 | 3705 | 10.67 | 2.79 | 51.3 | 4144 |
| Aluminum Conductor | ||||||||||||
| 1/0 | 53.5 | 8.53 | 16 | 14 | 8.76 | 2.03 | 39.4 | 1543 | 10.67 | 2.03 | 43 | 1755 |
| 2/0 | 67.4 | 9.55 | 13 | 12 | 8.76 | 2.03 | 41.3 | 1727 | 10.67 | 2.03 | 44.8 | 1944 |
| 3/0 | 85 | 10.7 | 16 | 12 | 8.76 | 2.03 | 42.4 | 1920 | 10.67 | 2.03 | 46 | 2143 |
| 4/0 | 107 | 12.1 | 13 | 10 | 8.76 | 2.03 | 44.9 | 2203 | 10.67 | 2.79 | 50.2 | 2631 |
| 250 | 127 | 13.2 | 16 | 10 | 8.76 | 2.03 | 46 | 2454 | 10.67 | 2.79 | 51.3 | 2893 |
| 350 | 177 | 15.6 | 16 | 9 | 8.76 | 2.79 | 50.8 | 3119 | 10.67 | 2.79 | 54.4 | 3381 |
15 kV Power Cable CU(AL)/XLPE/CWS/PVC One-third Neutral
| 15 kV Power Cable CU(AL)/XLPE/CWS/PVC One-third Neutral | ||||||||||||
| Conductor | One-third Neutral | 100% Insulation Level | 133% Insulation Level | |||||||||
| Size | Area | Nominal Diameter | No. of wires | Size | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| AWG/kcmil | mm² | mm | AWG | mm | mm | mm | kg/km | mm | mm | mm | kg/km | |
| Copper Conductor | ||||||||||||
| 2 | 33.6 | 6.81 | 9 | 16 | 4.45 | 2.03 | 26.9 | 933 | 5.59 | 2.03 | 29.4 | 1038 |
| 1 | 42.4 | 7.59 | 11 | 16 | 4.45 | 2.03 | 27.7 | 1062 | 5.59 | 2.03 | 30.2 | 1170 |
| 1/0 | 53.5 | 8.53 | 14 | 16 | 4.45 | 2.03 | 28.7 | 1228 | 5.59 | 2.03 | 31.2 | 1340 |
| 2/0 | 67.4 | 9.55 | 18 | 16 | 4.45 | 2.03 | 29.7 | 1435 | 5.59 | 2.03 | 32.2 | 1550 |
| 3/0 | 85 | 10.7 | 22 | 16 | 4.45 | 2.03 | 30.9 | 1682 | 5.59 | 2.03 | 33.4 | 1802 |
| 4/0 | 107 | 12.1 | 18 | 14 | 4.45 | 2.03 | 32.9 | 2013 | 5.59 | 2.03 | 35.4 | 2138 |
| 250 | 127 | 13.2 | 21 | 14 | 4.45 | 2.03 | 34 | 2284 | 5.59 | 2.03 | 36.5 | 2413 |
| 350 | 177 | 15.6 | 18 | 12 | 4.45 | 2.03 | 37.3 | 2977 | 5.59 | 2.03 | 40.4 | 3155 |
| 500 | 253 | 18.7 | 26 | 12 | 4.45 | 2.03 | 40.9 | 4049 | 5.59 | 2.03 | 43.4 | 4202 |
| 750 | 380 | 23.1 | 25 | 10 | 4.45 | 2.79 | 48.1 | 5971 | 5.59 | 2.79 | 50.6 | 6149 |
| 1000 | 507 | 26.9 | 32 | 10 | 4.45 | 2.79 | 52.4 | 7624 | 5.59 | 2.79 | 55.7 | 7900 |
| Aluminum Conductor | ||||||||||||
| 2 | 33.6 | 6.81 | 6 | 14 | 4.45 | 2.03 | 27.6 | 734 | 5.59 | 2.03 | 30.1 | 839 |
| 1 | 42.4 | 7.59 | 6 | 14 | 4.45 | 2.03 | 28.4 | 782 | 5.59 | 2.03 | 30.9 | 890 |
| 1/0 | 53.5 | 8.53 | 6 | 14 | 4.45 | 2.03 | 29.3 | 841 | 5.59 | 2.03 | 31.8 | 952 |
| 2/0 | 67.4 | 9.55 | 7 | 14 | 4.45 | 2.03 | 30.4 | 930 | 5.59 | 2.03 | 32.9 | 1045 |
| 3/0 | 85 | 10.7 | 9 | 14 | 4.45 | 2.03 | 31.5 | 1053 | 5.59 | 2.03 | 34 | 1172 |
| 4/0 | 107 | 12.1 | 11 | 14 | 4.45 | 2.03 | 32.9 | 1195 | 5.59 | 2.03 | 35.4 | 1320 |
| 250 | 127 | 13.2 | 13 | 14 | 4.45 | 2.03 | 34 | 1321 | 5.59 | 2.03 | 36.5 | 1450 |
| 350 | 177 | 15.6 | 18 | 14 | 4.45 | 2.03 | 36.4 | 1633 | 5.59 | 2.03 | 39.5 | 1810 |
| 500 | 253 | 18.7 | 16 | 12 | 4.45 | 2.03 | 40.9 | 2128 | 5.59 | 2.03 | 43.4 | 2280 |
| 750 | 380 | 23.1 | 24 | 12 | 4.45 | 2.79 | 47.1 | 3051 | 5.59 | 2.79 | 49.6 | 3230 |
| 1000 | 507 | 26.9 | 20 | 10 | 4.45 | 2.79 | 52.4 | 3819 | 5.59 | 2.79 | 55.7 | 4095 |
25 kV Power Cable CU(AL)/XLPE/CWS/PVC One-third Neutral
| 25 kV Power Cable CU(AL)/XLPE/CWS/PVC One-third Neutral | ||||||||||||
| Conductor | One-third Neutral | 100% Insulation Level | 133% Insulation Level | |||||||||
| Size | Area | Nominal Diameter | No. of wires | Size | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| AWG/kcmil | mm² | mm | AWG | mm | mm | mm | kg/km | mm | mm | mm | kg/km | |
| Copper Conductor | ||||||||||||
| 1 | 42.4 | 7.59 | 11 | 16 | 6.6 | 2.03 | 31.9 | 1242 | – | – | – | – |
| 1/0 | 53.5 | 8.53 | 14 | 16 | 6.6 | 2.03 | 33.2 | 1433 | 8.13 | 2.03 | 36.8 | 1619 |
| 2/0 | 67.4 | 9.55 | 18 | 16 | 6.6 | 2.03 | 34.2 | 1646 | 8.13 | 2.03 | 38.4 | 1877 |
| 3/0 | 85 | 10.7 | 22 | 16 | 6.6 | 2.03 | 35.4 | 1902 | 8.13 | 2.03 | 39.6 | 2140 |
| 4/0 | 107 | 12.1 | 18 | 14 | 6.6 | 2.03 | 37.4 | 2241 | 8.13 | 2.03 | 41.6 | 2488 |
| 250 | 127 | 13.2 | 21 | 14 | 6.6 | 2.03 | 39.1 | 2559 | 8.13 | 2.03 | 42.7 | 2773 |
| 350 | 177 | 15.6 | 18 | 12 | 6.6 | 2.03 | 42.4 | 3271 | 8.13 | 2.79 | 47.8 | 3687 |
| 500 | 253 | 18.7 | 26 | 12 | 6.6 | 2.03 | 45.4 | 4326 | 8.13 | 2.79 | 50.8 | 4771 |
| 750 | 380 | 23.1 | 25 | 10 | 6.6 | 2.79 | 52.6 | 6295 | 8.13 | 2.79 | 57 | 6660 |
| 1000 | 507 | 26.9 | 32 | 10 | 6.6 | 2.79 | 57.7 | 8061 | 8.13 | 2.79 | 61.3 | 8371 |
| Aluminum Conductor | ||||||||||||
| 1 | 42.4 | 7.59 | 6 | 14 | 6.6 | 2.03 | 32.9 | 980 | ||||
| 1/0 | 53.5 | 8.53 | 6 | 14 | 6.6 | 2.03 | 33.8 | 1045 | 8.13 | 2.03 | 37.4 | 1231 |
| 2/0 | 67.4 | 9.55 | 7 | 14 | 6.6 | 2.03 | 34.8 | 1142 | 8.13 | 2.03 | 39 | 1372 |
| 3/0 | 85 | 10.7 | 9 | 14 | 6.6 | 2.03 | 36 | 1272 | 8.13 | 2.03 | 40.2 | 1509 |
| 4/0 | 107 | 12.1 | 11 | 14 | 6.6 | 2.03 | 37.4 | 1424 | 8.13 | 2.03 | 41.6 | 1671 |
| 250 | 127 | 13.2 | 13 | 14 | 6.6 | 2.03 | 39.1 | 1596 | 8.13 | 2.03 | 42.7 | 1811 |
| 350 | 177 | 15.6 | 18 | 14 | 6.6 | 2.03 | 41.5 | 1926 | 8.13 | 2.03 | 45.1 | 2154 |
| 500 | 253 | 18.7 | 16 | 12 | 6.6 | 2.03 | 45.4 | 2405 | 8.13 | 2.79 | 50.8 | 2849 |
| 750 | 380 | 23.1 | 24 | 12 | 6.6 | 2.79 | 51.6 | 3375 | 8.13 | 2.79 | 56.1 | 3741 |
| 1000 | 507 | 26.9 | 20 | 10 | 6.6 | 2.79 | 57.7 | 4256 | 8.13 | 2.79 | 61.3 | 4566 |
35 kV Power Cable CU(AL)/XLPE/CWS/PVC One-third Neutral
| 35 kV Power Cable CU(AL)/XLPE/CWS/PVC One-third Neutral | ||||||||||||
| Conductor | One-third Neutral | 100% Insulation Level | 133% Insulation Level | |||||||||
| Size | Area | Nominal Diameter | No. of wires | Size | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| AWG/kcmil | mm² | mm | AWG | mm | mm | mm | kg/km | mm | mm | mm | kg/km | |
| Copper Conductor | ||||||||||||
| 1/0 | 53.5 | 8.53 | 14 | 16 | 8.76 | 2.03 | 38.7 | 1736 | 10.67 | 2.03 | 42.3 | 1947 |
| 2/0 | 67.4 | 9.55 | 18 | 16 | 8.76 | 2.03 | 39.8 | 1958 | 10.67 | 2.03 | 43.3 | 2175 |
| 3/0 | 85 | 10.7 | 22 | 16 | 8.76 | 2.03 | 41 | 2223 | 10.67 | 2.03 | 44.5 | 2447 |
| 4/0 | 107 | 12.1 | 18 | 14 | 8.76 | 2.03 | 43 | 2574 | 10.67 | 2.79 | 48.3 | 2995 |
| 250 | 127 | 13.2 | 21 | 14 | 8.76 | 2.03 | 44.1 | 2861 | 10.67 | 2.79 | 49.4 | 3292 |
| 350 | 177 | 15.6 | 18 | 12 | 8.76 | 2.79 | 49.2 | 3786 | 10.67 | 2.79 | 52.8 | 4049 |
| 500 | 253 | 18.7 | 26 | 12 | 8.76 | 2.79 | 52.2 | 4876 | 10.67 | 2.79 | 56.6 | 5239 |
| 750 | 380 | 23.1 | 25 | 10 | 8.76 | 2.79 | 58.4 | 6776 | 10.67 | 2.79 | 62 | 7082 |
| 1000 | 507 | 26.9 | 32 | 10 | 8.76 | 2.79 | 62.7 | 8496 | 10.67 | 2.79 | 66.2 | 8825 |
| Aluminum Conductor | ||||||||||||
| 1/0 | 53.5 | 8.53 | 6 | 14 | 8.76 | 2.03 | 39.4 | 1348 | 10.67 | 2.03 | 43 | 1559 |
| 2/0 | 67.4 | 9.55 | 7 | 14 | 8.76 | 2.03 | 40.4 | 1453 | 10.67 | 2.03 | 44 | 1670 |
| 3/0 | 85 | 10.7 | 9 | 14 | 8.76 | 2.03 | 41.6 | 1592 | 10.67 | 2.03 | 45.1 | 1815 |
| 4/0 | 107 | 12.1 | 11 | 14 | 8.76 | 2.03 | 43 | 1756 | 10.67 | 2.79 | 48.3 | 2177 |
| 250 | 127 | 13.2 | 13 | 14 | 8.76 | 2.03 | 44.1 | 1899 | 10.67 | 2.79 | 49.4 | 2330 |
| 350 | 177 | 15.6 | 18 | 14 | 8.76 | 2.79 | 48.3 | 2437 | 10.67 | 2.79 | 51.8 | 2699 |
| 500 | 253 | 18.7 | 16 | 12 | 8.76 | 2.79 | 52.2 | 2954 | 10.67 | 2.79 | 56.6 | 3317 |
| 750 | 380 | 23.1 | 24 | 12 | 8.76 | 2.79 | 57.5 | 3857 | 10.67 | 2.79 | 61 | 4164 |
| 1000 | 507 | 26.9 | 20 | 10 | 8.76 | 2.79 | 62.7 | 4691 | 10.67 | 2.79 | 66.2 | 5020 |